CONTROLS
BasicPowerFactor: The value at which that power factor is to be
set is selected by means of this control, which has a calibrated dial
from0.81agto 1.00.
DeadBand:Dependinguponthe KVARcapacityofeach capacitorto
be switched the, relay response sensitivityhas to be adjusted. The
dead band control serves to adjust this, so that hunting isavoided
DeadBandControl: . AtMinimum-::'::3° Electrical
AtMaximum- ::'::13°Electrical
SPECIFICATION
Voltage: 400 or 415 or 440V 3 Ph. 3. wire, 50 Hz, 2.5 VA(J ]OVAC.
forHTapplication).
Current: Through 5 Amp. CTsecondary on RPhase of incomer.3VA
(1Amp model on request).
Output: Each capacitor control relay is provided with one change
over contaa rated formaximum 230VAC/5Amps.resistive
load.
P.FA. djustment range: 0.81agto 1.00.
P.F. Meter range: 0.61agto 0.6Iead.
APFCR – TYPE 144.

- Built in analog / digital P. F. meters
- Calibrated setting dial
- Dead band setting
- Built in auto/ manual switching
- Cycle switching
- Indicating leds for each capacitor switching modules
- A uniquetiming action that follows the charge /discharge of the controlled capacitor
- Fully solid state reliability.
Top
MICROPROCESSOR APFCR – 1304 & 1305
General :
Power Factor is an important Electrical parameter needing control,State of theart microcontrolbased APFCR type 130 5is specially designed to control the powerfactor of aninstallation by giving signals to switch capacitors on and of in a FIFO/FILOmanner accordinglyandreliably. The controller is ~ousedin a COQ1pac Ftlush Panelmounting enclosure of size144x 144DIN and has all the required controls and indications arranged on the front panel. High barrier /
shroud edterminals are provided attherear of the casefor external connections. Solid state comonents are used through out with the exception of the electromechanical relays for the externals witch in gfor high reliability and compactness.The constructionis rugged, designed for years of troublefree service.
Features
Micro control Field proven design.
- Available in 4, 8, 12,16,stages.
- Accurate measurement & user Friendly operation
- Built in Auto/ Manual control.
- Calibrated PF setting & deadband.
- Built in digital timer for fast operation ensures capacitor safety.
- Built in self/test facility.
- Auto detection for low current & external wrong connection indicatonon
- Control power factordirectlyregardlessofsizeofcapacitor.
- Low current cut off at1%.
- Choice of sequence FIFO/FILO/Bina(ray.nyone)
- Available for LT & HT application.
- Compact DIN std flush mounting144mmx144mmx 1OOmm depth
|